Infloor® tubes are embedded directly in the concrete slab or soil. Due to the high Cv
rating (14.4), the High Capacity manifolds can service one or two 450-foot (135 m) lengths
of 1/2" (13 mm) tube; or one 1,000-foot (300 m) length of 3/4" (19 mm) tube per manifold
section. With eight supply/return modules, reset control with sensors, circulating pump,
air vents and drains, preassembled High Capacity manifolds can deliver up to 300,000 Btu/hr
(88,000 W).
|
| Characteristics |
PEX |
BPEX |
| Performance Characteristic |
ASTM 876 |
ASTM 876 |
| SDR |
9 |
9 |
| Oxygen Barrier |
---- |
EVOH |
| DIN |
---- |
4726 |
| PSI |
100 (689 kPa) |
100 (689 kPa) |
| Temperature |
180 °F (82 °C) |
180 °F (82 °C) |
| Linear Expansion |
1.1 in./(10 °F 100 ft) |
1.1 in./(10 °F 100 ft) |
| Thermal Conductivity |
2.7 Btu in./hr ft(squared) °F |
2.7 Btu in./hr ft(squared) °F |
Quick Burst Strength @ 73 °F |
440 psi |
440 psi |
| Sizes |
3/8"(10 mm) 1/2"(13 mm) 3/4"(19 mm) |
3/8"(10 mm) 1/2"(13 mm) 3/4"(19 mm) |
Bend Radius 3/8" 1/2" 3/4" |
6 x o.d. 6 x o.d. 6 x o.d. |
6 x o.d. 6 x o.d. 6 x o.d. |
| Warranty |
25 yrs. |
25 yrs. |